A suspended ceiling is ordered from the area of the room. The boards or tiles follow from the area and their size; the frame follows from the spacings that the maker of the system gives. This guide counts quantities; it does not design the ceiling.

1. Area and edge

Multiply the room length by its width. The edge channel or wall angle runs round the room: twice the length plus the width.

Using the tool step by step

The numbered marks on the screenshots follow the order in which you use the tool. The fields are filled with an example.

  1. False Ceiling Quantities (boards, furring, tiles): step 1
    Step 1 Enter your values: dimensions, materials and options.
  2. False Ceiling Quantities (boards, furring, tiles): step 2
    Step 2 Read the results: quantities, costs and estimated durations, updated as you type.
  3. False Ceiling Quantities (boards, furring, tiles): step 3
    Step 3 Before: the plan of the work to be built, with its dimensions.
  4. False Ceiling Quantities (boards, furring, tiles): step 4
    Step 4 After: the 3D rendering of the finished work (an illustration made by the tool, not a photo).

2. Boards, furring and hangers

Divide the area, increased by the waste, by the area of one board. The furring runs at its spacing, so its length is the area divided by that spacing. One hanger serves the area of the furring spacing times the hanger spacing along it: divide the ceiling area by that and round up.

Worked example: 6 × 4 m room

Boards 1.20 × 2.50 m, furring every 60 cm in 3 m bars, hangers every 1.20 m, 10 % waste, 15 screws and 0.4 kg of compound per m²:

  • Area 6 × 4 = 24 m², edge channel 20 m.
  • Boards: 24 × 1.10 ÷ 3 = 8.8, so 9 boards.
  • Furring: 24 ÷ 0.6 = 40 m, or 14 bars of 3 m.
  • Hangers: 24 ÷ (0.6 × 1.2) = 33.3, so 34.
  • Screws 360; jointing compound 9.6 kg.

Lay-in tiles on a grid

For 60 × 60 cm tiles there is a line of profile every 60 cm in both directions: 1/0.6 + 1/0.6 = 3.33 m of profile per m². Main runners every 1.20 m carry the cross tees, and the hangers hang from the main runners.

What this does not cover

The count does not design the ceiling: the frame, the load a hanger carries, the fire, acoustic and humidity requirements and the board type come from the maker’s data and the engineer.

General information, checked at the date shown. It does not replace advice from a professional for your situation.